Wall mount CO transmitter
CMWNL Room CO transmitter Output RS485/MOdbus Range 0 0~100ppm
Also available options 0-10VDC, 4-20mAs, 0-300ppm and LCD display.
Specifications
CO sensor: Electrochemical, >5 years life span
Sampling Method: Diffusion
Range: 0~100ppm
Accuracy: ±5% FS@25°C, typical ±10% FS@5~50°C
Repeatability: <±3%FS
Stability: <±5%/year@0-100ppm, <±10%/year@0-300ppm
Response time (T90): <60s
Warm-up time: <1 min
Load Resistance: ≤500Ω (current output), ≥2Kω (voltage output)
Power: Current: 18.5~35VDC(RL=500Ω), 8.5~35VDC(RL=0Ω)
Voltage: 16~28VAC/16~35VDC
Output: 4~20mA (2 wires), 0-10VDC, RS485/Modbus
Work environment: 5~50°C(continuous), 15~90%RH(Non- cond.)
Storage Temperature: -10~55°C
Housing: fire retardant PC(UL94V-0) (CMWNL),
fire retardant ABS+PC(UL94V-0) (CMWL)
Protection: IP33 (CMWL), IP30 (CMWNL)
Weight: 190g (CMWL), 160g(CMWNL)
Agency Approval: CE